(A)A residential
facility shall secure a JFS 01200 "Fire Inspection Report Child Care
Facilities Licensed/Certified by the Ohio Department of Job and Family
Services" (rev. 10/200002/2015) fire safety approval or other form used for a
local or state fire inspection in each of the following instances:
(1)Within six
months prior to initial certification.
(2)At the time of
any major modification or alteration of any existing structure, unless the
structure will no longer be in use and is inaccessible to children.
(3)Not more than
twelve months following the date of the previous inspection.
(B)A residential
facility shall not be certified or recertified without an approved fire safety
inspection obtained pursuant to paragraph (A) of this rule.
(C)All fire
safety approvals shall be secured from the state fire marshal or from a
township or municipal fire department which has personnel certified to inspect
and approve the fire and building code use group applicable to the residential
facility.
(D)Each
residential facility shall have smoke detectors located according to
instructions of the local fire safety inspector or state fire marshal.
(E)Each smoke
detector located in a residential facility shall be tested at least twice
annually at regularly spaced intervals. Such testing shall be documented in a
log which indicates the date of the test, the results, and action taken if the
result of the test indicated that the smoke detector was inoperable or
malfunctioning. If the facility has a combined smoke detector and fire alarm
system a fire alarm inspection shall be conducted by a company approved to test
such equipment at least twice annually at regularly spaced intervals or
approved by local or state fire inspector. The facility shall obtain annual
alarm system testing and shall have documentation of testing.
(F)Each
residential facility shall have fire extinguishers in specific locations as
required by the certified fire inspector. Fire extinguishers shall be inspected
as required by the fire inspector and documentation maintained.
(G)No residential
facility shall allow candles to be burned in sleeping areas.
(H)Free-standing
wood-burning stoves and unvented heaters that burn kerosene, gas or oil shall
not be used in a residential facility.
(I)Portable
heaters may be used and maintained in accordance with manufacturer's
instructions, if the heater has been approved by the underwriter's laboratory,
and are not prohibited by any local or state ordinances or fire inspector.
Effective: 2/1/2020
Five Year Review (FYR) Dates: 6/13/2019 and 02/01/2025
Certification: CERTIFIED ELECTRONICALLY
Date: 01/17/2020
Promulgated Under: 119.03
Statutory Authority: 5103.03
Rule Amplifies: 5103.02, 5103.03
Prior Effective Dates: 12/30/1966, 10/01/1986, 01/01/1991,
09/18/1996, 09/01/2002, 01/01/2008, 12/01/2010, 07/01/2014